【篇名】 Detailed analysis of PCBs and PCDD/Fs impurities in a dielectric oil sample (ASKAREL Nr 1740) from an imported transformer in China
【刊名】 Frontiers of Environmental Science and Engineering in China
【刊名缩写】 Front.Environ.Sci.Engin.China
【ISSN】 2095-2201
【EISSN】 2095-221X
【DOI】 10.1007/s11783-013-0527-y
【出版社】 Higher Education Press and Springer-Verlag Berlin Heidelberg
【出版年】 2014
【卷期】 8 卷2期
【页码】 195-204 页,共 10 页
【作者】 Jun HUANG; Yamei HUI; Toru MATSUMURA; Gang YU; Shubo DENG; Makoto YAMAUCHI; Changmin WU; Norimasa YAMAZAKI;
【关键词】 profiles of polychlorinated biphenyls (PCBs); polychlorinated dibenzo-p-dioxins (PCDDs); polychlorinated dibenzofurans (PCDFs); Askarel transformer; insulating fluid

【摘要】
Homolog and congener profiles of polychlorinated biphenyls (PCBs), polychlorinated dibenzo-p- dioxins (PCDDs) and polychlorinated dibenzofurans (PCDFs) in commercial PCBs formulations are useful information for the source appointment of PCBs contamination as well as the risk assessment caused by potential exposure. Dielectric oil (ASKAREL Nr 1740) in an imported transformer found in China was sampled and analyzed by isotope dilution technology using high resolution gas chromatography-high resolution mass spectrometry (HRGC/HRMS). The detailed homolog and congener profiles of PCBs obtained were compared with those of known Aroclor formulations. High similarity in the homolog profile between the oil sample and Aroclor 1260?was found, with the hexachlorinated and heptachlorinated biphenyls accounting for more than 80.2% of the total PCBs concentration. Severn indicator PCBs contribute about 30%, while 12 PCB congeners (i.e., #153, #143, #168, #180, #149, #165, #138, #170, #190, #187, #174, #181) account for more than 50% of the total PCB concentrations. Total concentration of PCDDs, PCDFs and dioxin-like PCBs (DL-PCBs) was found to be 740?ng TEQ/g, of which 620?ng TEQ/g came from DL-PCBs. The contribution of PCDDs to the total TEQ was neglectable. The concentration of PCDFs homologs follows the order of OCDF>HxCDFs>HpCDFs>PeCDFs>TeCDFs, which is in consistence with the previous study on Aroclor 1260. Three DL-PCBs congeners (i.e., #118, #156, #157) accounted for 77% of the total concentration of DL-PCBs, also they contribute 72% in the TEQ caused by DL-PCBs.
版权所有 © CALIS管理中心 2008